Кол-центр: +375 17 378 09 05

VACUUM RECLOSER
РВ-БЭМН


   Purpose
For automatic disconnection of a damage part of a network, remote control,
automatic power backup input and automatic reclosure.

   Field of application
10 кВ aerial lines with one-way and two-way power supple.

   Features
A recloser constantly controls current and voltage, performs relay protection
functions, by means of a GSM modem may be integrated in Smart Grid system
procuring an opportunity to separate a damaged, as well as manual and computer-
aided dispatcher control. Its application makes it possible to reduce time
for detecting, localizing and removing an electric line damage and, therefore,
improve reliability of power supply for customers and reduce operational costs.

  Configuration
• A switching unit with built-in current transformers.
• An auxiliary transformer.
• A control cabinet with МР750 current directional protection terminal (or
МР550 current indirectional protection terminal), GSM modem, battery and
a heater.
• An instrumentation cable with switching plugs for connecting the cabinet to
a reclouser.
• A feed cable for connecting an auxiliary transformer to the cabinet.
• Excess-voltage suppressors.
• A mounting kit.
Against order РВ-БЭМН reclouser may be equipped with a commercial accounting
unit with the following configuration:
• a cabinet of measuring transformers;
• an accounting cabinet with a power meter and GSM modem.Purpose
For automatic disconnection of a damage part of a network, remote control,
automatic power backup input and automatic reclosure.
Field of application
10 кВ aerial lines with one-way and two-way power supple.
Features
A recloser constantly controls current and voltage, performs relay protection
functions, by means of a GSM modem may be integrated in Smart Grid system
procuring an opportunity to separate a damaged, as well as manual and computer-
aided dispatcher control. Its application makes it possible to reduce time
for detecting, localizing and removing an electric line damage and, therefore,
improve reliability of power supply for customers and reduce operational costs.
Configuration
• A switching unit with built-in current transformers.
• An auxiliary transformer.
• A control cabinet with МР750 current directional protection terminal (or
МР550 current indirectional protection terminal), GSM modem, battery and
a heater.
• An instrumentation cable with switching plugs for connecting the cabinet to
a reclouser.
• A feed cable for connecting an auxiliary transformer to the cabinet.
• Excess-voltage suppressors.
• A mounting kit.
Against order РВ-БЭМН reclouser may be equipped with a commercial accounting
unit with the following configuration:
• a cabinet of measuring transformers;
• an accounting cabinet with a power meter and GSM modem.

Specifications

Parameter

                 Value                

Rated voltage, kV

10

Highest working voltage, kV

12

Rated current, А

630

Rated breaking current, kA

20

Rated frequency, Hz

50

Thermal capability current (within 4 s), kA, at least

20

Rated voltage of control circuits (DC), V

48 or 24

Mechanical service life, “I–О”

10000

Switching service life:

 

10000

•    at rated current, “I–О” operations

•    at rated breaking current, “I–О” operations, at least

50

Switching unit opening time, ms

45–80

Proper time of relay protection operation, ms

50

Lighting impulse test voltage, kV

75

One-minute test arc line voltage, kV

42

Switching unit protection degree, МЭК 529-89

IРХ6

Operative power supply source:

 

200

•    Output capacity (sustained), V·А, not exceeding

•    Rated consumed power (in the spring windup mode), V·A, not exceeding

500

•    AC operative power supply voltage, V

230

Uninterrupted power supply system:

 

48(4´12)

•    Battery rated voltage, V

•    Battery rated capacity, А·h

12

•    Time of operation when supplied by live battery after operative power supply failure, h, at least

24

•    Number of “I–О” cycles when supplied by live battery

50